What is a fire door for?
It compartmentalises a building: in a fire, it holds back flames, heat and smoke in the area where the fire started, giving time to evacuate people and for the fire service to act. You find it between two storage cells, at the entrance to a high-risk room (boiler room, battery charging room), in buildings open to the public or between a workshop and offices.
A fire door is not a “reinforced” door: it is a tested and classified assembly, frame, leaf, hardware and seals included. Replacing a single part with a component not designed for it can cause it to lose its classification.
What does the EI classification of a fire door mean?
The European classification, defined by EN 13501-2, states what the door guarantees and for how many minutes. The letter E stands for integrity against flames and hot gases, the letter I for thermal insulation (the unexposed face must stay below a certain temperature). The number that follows is the duration in minutes: EI 30, EI 60, EI 120…
| Code | Meaning |
|---|---|
| E | Integrity: flames and hot gases do not pass |
| I | Thermal insulation: the protected face stays below a temperature threshold |
| Duration (30, 60, 120…) | Time for which the criteria are met during the test |
| C | Self-closing: the door closes by itself |
| S | Limited leakage of cold smoke |
The old French designations “PF” (pare-flammes, integrity only) and “CF” (coupe-feu, fire-resistant), expressed in hours, still appear on older doors. The classification required for your opening is set by the regulations that apply to the building, the inspection body or the insurer: we do not choose it for you.
What types of fire doors are there?
Doors that stay open in normal use are held by an electromagnetic hold-open or a release device linked to the fire detection: on alarm or power cut, they are released and close. DEPANN'Rideaux fits, maintains and repairs all three types of fire door, all makes. For a new installation, we offer products certified for the required classification; the chosen model and its specifications are set out in the quote.
How should a fire door be checked and maintained?
A fire door is checked to confirm one thing: that it will close fully, by itself, on the day of a fire. The check covers the door closer, the closing sequence selector, the condition of the intumescent seals, the hardware, the gap between leaf and frame, release by the detection system and the absence of obstacles.
In buildings open to the public in France, these doors are checked under the fire safety regulations. Automatic and semi-automatic doors in a workplace must also be maintained and checked at least every six months (French Labour Code, articles R4224-12 and R4224-13, and the order of 21 December 1993). After each visit, the work can be recorded in the maintenance log: see industrial door maintenance and our guide to mandatory maintenance of closures.
What should you do if your fire door no longer closes?
Call a technician quickly: a fire door that does not close protects nothing. Common causes: a worn door closer, a leaf warped by an impact, a misadjusted selector, a hold-open that no longer releases the door. On +33 7 68 20 39 55, describe the fault: the technician gives you safety instructions and tells you how soon they can be there. The price is given to you on site, after the diagnosis and before any work starts; if you decline the work after the diagnosis, only the call-out is charged. What to do is set out on the industrial door repair page.
We work on industrial sites, warehouses and public buildings in Rouen, Le Havre, Caen and all of Normandy. For the other closures in your building, such as the industrial sectional door, see our industrial doors page.